MODEL DVR (ROUND) TYPE-B
GAS VENT INSTALLATION
INSTRUCTIONS
Read through all of these instructions before beginning your installation.
Failure to install as described in these instructions will void the manufacturer’s
warranty and may have an effect on your homeowner’s insurance and UL
listing status. Keep these instructions for future reference.
REFERENCES
(1) National Fuel Gas Code, also referred to as NFPA 54 and ANSI Z223.1
(2) Simpson Dura-Vent's Sizing Handbook, available from Simpson Dura-
Vent
CONTENTS
REFERENCES .......................................................................................... 1
GENERAL INFORMATION.................................................................. 1
PLANNING ............................................................................................... 2
STEPS FOR TYPICAL INSTALLATION ........................................... 4
BUCKET SUPPORT ................................................................................ 9
COMBINATION TOP ........................................................................... 10
ADJUSTABLE ELBOWS...................................................................... 11
MALE AND FEMALE ADAPTORS .................................................. 12
RELINING MASONRY CHIMNEYS .................................................. 13
MAINTENANCE .................................................................................... 19
GENERAL INFORMATION
Type B Gas Vents are for venting listed Natural Gas or Liquid Propane
Category I appliances only. The appliances listed below typically (but not always)
use Type B vent systems.
Boilers Furnaces
Water Heaters Unit Heaters
Room Heaters Duct Furnaces
Floor Furnaces Decorative Gas Appliances
Simpson Dura-Vent Type B Vent Systems may be used on other gas-burning
appliances, provided the manufacturer of the appliance states in their installation
instructions that Type B-vent is acceptable. Do not use Type B Vents for Category
MH6357
Zobrazit stránku 0
1 2 3 4 5 6 ... 19 20

Shrnutí obsahu

Strany 1

1MODEL DVR (ROUND) TYPE-BGAS VENT INSTALLATIONINSTRUCTIONSRead through all of these instructions before beginning your installation.Failure to in

Strany 2

10nail into place. Run the Pipe Sections through the hole in the Bucket Support,connect the Dura-Connect Single Wall Connector, and attach the Clamp

Strany 3

11and seal with a non-hardening sealant, as shown in Figure 17. Seal all nailheads.5. Height. Add sufficient Pipe Sections of B-Vent until the sys

Strany 4

12does no longer have a 90° angle.4. 45° Offsets with 90° Elbows.Figure 21 shows a 90° AdjustableElbow being utilized to accomplish a45° offset. Thi

Strany 5

13RELINING MASONRYCHIMNEYS FOR USE WITHGAS APPLIANCES1. Description. A masonry chim-ney should be relined with B-Ventwhen venting a Category I g

Strany 6

14in your measurements.(b) Pipe andFitting Requirements.The bottom 5 foot sectionof vent will be Flex Pipe(used to get around thesmoke shelf, and toc

Strany 7

15Fireplace. Push the gas fireplace towards thefirebox, and connect the Flex Pipe female cou-pling to the appliance, or to the appropriateconnector as

Strany 8

16large enough to reach through and hold the Tee, while connecting the horizontalPipe Section. An alternate procedure is to make the hole only large

Strany 9

17through the access door while someone twist-locks the Pipe Section to it. Usean Adjustable Pipe Length as needed to obtain a specific location for

Strany 10

18vent cap.4. Blockage. Check the system for blockage by removing the cap, andlooking down into the vent with a flashlight. Check for bird nests, de

Strany 11

19prevent rusting and corrosion on the exterior surfaces.MAINTENANCE1. An annual inspection is required to maintain warranty of yourSimpson Dura-Vent

Strany 12

2FLASHINGHIGH WIND TOPDuraCap TOPSEE TABLE 21 INCH MINIMUMCLEARANCE(ALL SIDES)B-VENT1 INCH MINIMUMCLEARANCE(ALL SIDES)FIRESTOPSPACERDOTTED LINES SHOW

Strany 13

20SIMPSONDURA-VENT, INCPO Box 1510Vacaville, CA95688-1510Vicksburg, MS (800)-835-4429 (707)-446-4740 (FAX)April 2000L204ASimpson Dura-Vent offers t

Strany 14

33. Figures 1, 2, & 3show examples of sometypical residential in-stallations.4. Clearance toCombustibles. A 1-inchclearance (air space) tocombu

Strany 15

4is within 8 feet. Vent pipe with 14" or larger diameter must terminate at least2 feet higher than an adjacent wall or obstruction, if it is wi

Strany 16

5Firestop Supports arecurrently manufactured forpipe sizes of 3" through 12"only. Larger sizes may belocally fabricated from sheetmetal, pr

Strany 17 - INSULATION

68" diameter pipe. However, if desired, use 1/4-inch long sheet metal screws for 3" through 8"diameter pipe. Never penetrate the inne

Strany 18

7be used in many applications when aB-Vent connector is not required.7. Elbows. When Elbows are re-quired, strap the Pipe Sections and/orElbows in pl

Strany 19

8clearance (air space) of 1 inchbetween the Pipe and construc-tion materials. Straight lengthsof pipe are run up above theroof. (see table 2) A Roof

Strany 20

9pletes the installation steps.Conduct a final inspection toinsure that all joints are se-cure, the system is properlysupported, and is mechani-cally